Herunterladen Inhalt Inhalt Diese Seite drucken

Maintenance; Inspection And Maintenance; Repair - AWG S2 Originalbetriebsanleitung

Schaumstrahlrohre
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

AWG I Operating manual I Fittings I
6.2.3
ADVANCED Inspection every 12 months
Check the coupling torque of the Storz adapter:
Threshold value
If the coupling torque is below the applicable threshold value, the
adapter must be replaced.
Threaded version: Check the thread for heavy wear and tear.
Replace device if worn.
7

MAINTENANCE

7.1

Inspection and maintenance

Apart from the visual inspection and cleaning of the AWG Foam noz-
zles, no regular maintenance work is required.
7.2

Repair

1
Protection ring
2
Internal thread screw
3
Disc
4
Cylinder head screw
Fig. 3
Repair
M1106B10 I Rev. 02-03/20
Low expansion foam nozzles S2, S4, S8
Storz 52 (C): 1.5 Nm
Storz 75 (C): 2.5 Nm
ENGLISH
5
Handle S8
6
Hand lever (option)
7
Disc
8
Screw
MAINTENANCE