Herunterladen Inhalt Inhalt Diese Seite drucken

Performing The Inspection - AWG S2 Originalbetriebsanleitung

Schaumstrahlrohre
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

AWG I Operating manual I Fittings I
Documenting the inspection result
To meet the requirements for occupational safety and acci-
dent prevention, the test results for each test must be doc-
umented. Please observe the country-specific regulations.
In Germany, the guidelines of the DGUV (Deutsche Gesetz-
liche Unfallversicherung e.V. [German Statutory Accident
Insurance]) apply. A product specific test chart in accord-
ance with the DGUV can be downloaded from www.awg-
fittings.com
– Keep the documented test result as proof.
6.2

Performing the inspection

CAUTION
Performing the inspection safely
Some inspection steps are performed with pressurised systems.
– Observe the safety regulations.
– Wear personal protective equipment.
– Do not put other persons in danger.
6.2.1
BASIC Inspection after each use
1. Inspect the foam nozzle for visible damage.
2. Check that the hand lever can be operated (unpressurised).
6.2.2
STANDARD Inspection every 12 months
1. Functional test of the stop valve (option) under dynamic load at
10 bar inlet pressure.
2. Leak test at 10 bar inlet pressure (with the hand lever in closed
position, if applicable).
3. Inspect the conversion screen for damage.