The two single components measuring cell and electronics both have a non-volatile
memory (EEPROM). Each contains a data structure which is permanently assigned
to the measuring cell or the electronics. Measuring cell data (e.g.: measuring range,
measuring cell material, oil filling etc.) are stored in the measuring cell's EEPROM.
Data of electronics (e.g.: turn-down, electric damping etc.) are in the electronic's 
EEPROM. Using the mode "factory calibration", please note that after exchanging a
component, the parameters seen in Table 2, page 49 are restored with the stated
values.
Condition of customer parameters
after exchange of electronic
Condition of customer parameters
after exchange of measuring cell
Parameters in SIMATIC PDM
Operation Unit / TAG
Device / Sensor Serial number
Unit and measuring speed / Unit
Unit and measuring speed / Cycle time
Measuring Limits / Measuring Range Min.
Measuring Limits / Lower Value Min / Upper Value Max.
Process Value Scale / Lower Value, Upper Value
Analog Output Limits / Analog Output Lower, Upper Endpoint
Value
Alarm states / AO Alarm type
Alarm states / Alarm LRV, URV
Damping
Linearization / Transfer function
Linearization / Start-point of square-rooting
Human Interface / Unit tracking
Table 1
Condition of customer parameters after exchange (HART Device)
A5E00078060-04
customer data
measuring cell
1)
factory data
2)
measuring cell
1
preseted
factory data
electronic
preseted
customer data
electronic
X
X
X
X
X
X
X
X
X
X
X
X
X
X
1
47