3 Function

The isolating power Supplies are used in the operation of 2-wire and 3-wire transmitters or
to connect to intrinsically safe mA current sources.
The 2-wire and 3-wire transmitters are supplied with power by the transmitter power supply
unit. The devices bidirectionally transfer a superimposed HART communications signal.

4 Marking and technical data

Manufacturer
Type designation
CE marking
ATEX explosion protection marking
and
Testing authority and certificate number
Ambient temperature range
Safety data
Max. voltage U
Max. current, I
Max. power, P
Internal capacitance C
Max. connectable capacitance, C
Max. connectable inductance, L
Insulation voltage U
See EC-type examination certificate for further information and value combinations
Technical data (extract from the data sheet)
Power supply
Nominal voltage U
Nominal current (at U
Power consumption (at U
Ex i input
Supply voltage for transmitter
Input signal range
Output
Range for load resistance
Output signal range
Ambient conditions
Operating temperature
Storage temperature
Relative humidity (no condensation)
Further technical information can be obtained from the current data sheet.
SITRANS I100
12
Operating instruction A5E02591611-02
Downloaded from
www.Manualslib.com
SIEMENS
R. STAHL
o
o
o
/ inductance L
i
i
IIC/IIB
o
IIC / IIB
o
m
N
and I
)
N
Amax
and I
)
N
Amax
Please consult with the manufacturer before operating under conditions which deviate
from the standard operating conditions.
manuals search engine
R. STAHL for SIEMENS
SITRANS I100 7NG4124-0AA00
9160/13-11-11
C
0158
E II 3 (1) G Ex nA nC [ia] IIC T4
E II (1) D [Ex iaD]
DMT 03 ATEX E 010 X
-20 ° C ... +60 (+70) ° C
(see chapter 5.1)
27 V
88 mA
576 mW
negligible
90 nF / 705 nF
2.3 mH / 14 mH
253 V
24 VDC
70 mA
1.7 W
16 V
0/4...20 mA
600 Ω
0/4...20 mA
-20...+60 (+70) ° C
-40...+80 ° C
< 95 %