Scaling of the measuring range (analogue output)
• With the parameter analogue start point (ASP) you define at which
measured value the output signal is 4 mA.
• With the parameter analogue end point (AEP) you define at which
measured value the output signal is 20 mA.
The analogue end point (AEP) can be selected so that it is located befo-
re the analogue start point (ASP). This implements a falling edge.
Current output 4 ... 20 mA
I [mA]
20
4
0(ASP)
MEW = final value of the measuring range
In the set measuring range the output signal is between 4 and 20 mA.
It is also signalled:
• Distance value outside the analogue start point (ASP): 3.5 mA
• Distance value outside the analogue end point (AEP): 20.5 mA
26
Downloaded from
www.Manualslib.com
Factory setting
10000(AEP)
manuals search engine
Measuring range scaled
I [mA]
20
4
mm
0
ASP
AEP
MEW
mm