Display unit
Measured value and values for SP1, SP2, ASP, AEP can be indica-
ted in the following units:
• mm, m, inch
Select the display unit before you define the values for the para-
meters SP1, SP2, ASP, AEP. This avoids rounding errors during
internal conversion to other units and enables exact setting of
the values.
When delivered: mm, the selected unit is indicated by a green
LED on the display.
Restore basic settings (factory settings)
- Press the "Mode/Enter" button until rES is displayed.
- Press the "Set" button and keep it pressed until "- - - -"
is displayed.
- Press the "Mode/Enter" button briefly (→ the unit passes into
the Run mode).
The unit is delivered with the following factory settings:
• Unit of mesurement mm
• Sp1: 1000 mm
• Sp2: 2000 mm
• OU1: Hno (normally open)
• OU2: Hno (normally open)
• ASP: 0 mm
• AEP: 9999 mm
• Sampling rate: 50 Hz
• Delay: 0 s
• Display update d3 (600 ms)
Display of the software version number