Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic EFECTOR PMD O1D100 Bedienungsanleitung Seite 23

Optischer abstandssensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Downloaded from
www.Manualslib.com
Delay for the switching outputs
dSx = switch-on delay; drx = switch-off delay.
The output does not immediately change its switching status
when the switching condition is met but only after the delay has
elapsed. If the switching condition is no longer met after the
delay has elapsed, the switching status of the output does not
change.
• Setting range: 0 / 0.1 ... 5 s in steps of 0.1 s
(0 = delay is not active);
• Indication in seconds
dS2 and dr2 are not effective if OU2 = I.
Display setting
7 settings can be selected:
d1
= update of the measured value every 50 ms
d2
= update of the measured value every 200 ms
d3
= update of the measured value every 600 ms
The update of the measured value only refers to the display. It
has no effect on the outputs.
rd1, rd2, rd3 = display like d1, d2, d3, but rotated by 180°.
OFF = The measured value display is deactivated in the Run
mode.
Press one of the buttons to indicate the current measured value
for 15 s. If the Mode/Enter button is pressed once again, the dis-
play mode is activated. The LEDs remain active even if the display
is deactivated.
Indication of the signal strength in %
Check the sensor alignment, if necessary.
manuals search engine
23

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis