Mounting and Connection Instructions IDENTLOC Evaluation Unit
7.8

Teaching mode

The teaching mode must be carried out
Ÿ
During initial commissioning
Ÿ
After every alteration

7.8.1 Function

In
teaching mode
, the sensor inputs 1 to 5 are checked for correctly functioning sensors.
Inputs 1 to 4:
T
he code
This means that data codes that have once been stored, remain stored when the EU is degenerized.
Input 5:
The EU checks whether a sensor is connected with 12k1

7.8.2 Run Teaching mode , EU operating mode "IDENTLOC"

Close the housing of the EU (the cover contact must be closed). Run Teaching mode via the control panel programming,
function 405 (see Programming Instruction 561-MB24/48/100).
- or
Run Teaching mode as described in the following Chapter.
7.8.3
Run Teaching mode
Ÿ Activate teaching mode
A) Without connection to control panel (also for programming master mode)
-
Connect operating voltage 12 V DC (e.g. accumulator)
-
The cover contact must be open.
- Switch position S2/2 = "OFF" (BUS-1):
LED "Totalling indicator" (red) lights up.
- Switch position S2/2 = "ON" (BUS-2):
LED "Totalling indicator" (red) does not light up.
-
Switch S1/8 to "ON".
The LED "Teaching mode" (yellow) lights up.
The LED "Totalling indicator" (red) also lights up at
switch position S2/2 = "ON" (BUS-2).
Teaching mode is now activated.
B) With connection to control panel
-
Operating voltage and BUS are connected to the control
panel. BUS communication is possible.
-
The cover contact must be open.
The opened cover contact triggers a tamper alarm at the
control panel.
The "Totalling indicator" (red) lights up
-
Switch S1/8 to "ON".
The LED "Teaching mode" (yellow) lights up.
Teaching mode is now activated.
(add, remove or exchange sensor)
of each connected sensor is read from the data telegram and stored in
, EU standard operating mode or master mode
end of line
resistor.
(see 7.2)
BUS-2/1
LED
totalling
indicator
LED
Teaching mode
BUS-2
BUS-1
S2
LM
NM
S1
ON
LED
Sensor 5
27
a non-volatile storage.
BUS-2/1
LED
Sensor 1
LED
Sensor 2
LED
Sensor 3
LED
Sensor 4

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis