5 Annex
5.1.2
Display
Type
Resolution
5.1.3
Electrical data
Voltage supply
Connection
Voltage
Residual ripple
Current consumption
Power consumption
Conductor cross section (voltage supply)
Wire or stranded wire without ferrule
Stranded wire with ferrule
2 × stranded wire with twin core-end
ferrule with plastic collar
Stripping length
Electrical safety
Protection rating
Electromagnetic compatibility
Interference emission
Interference immunity
Data backup
Buffer battery service life
5.1.4
Housing and environmental conditions
Case type
Dimensions (W × H × D)
Weight (fully fitted)
Protection type
Ambient temperature range
Storage temperature range
Resistance to climatic conditions
Site altitude
30
LCD, monochrome
96 × 64 pixels (8 rows)
At the front (removable terminal strip, 2-pole with Push-In technolo-
gy)
DC 24 V +25/-20 % SELV
5 %
Max. 1.16 A (at DC 19.2 V)
Current consumption of lined-up modules also has to be considered
(see "Hardware configuration" in the setup program)!
Max. 25 W
2
Min. 1.5 mm
, max. 2.5 mm
2
Min. 1.5 mm
, max. 2.5 mm
2
1.5 mm
10 mm
According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
III
Acc. to DIN EN 61326-1
Class A - only for industrial use -
Industrial requirement
Buffered RAM
Approx. 6 years (lithium battery)
Observe fault messages on battery status in the event list (battery al-
most empty, battery empty)!
Plastic case for DIN rail mounting in the control cabinet (indoor use);
DIN rail acc. to
DIN EN 60715, 35 mm x 7.5 mm x 1 mm
135 mm × 101 mm × 101.5 mm (without connection elements)
Approx. 590 g
IP 20, according to DIN EN 60529
-20 to +55 °C
-40 to +70 °C
Relative humidity ≤ 90 % annual average without condensation (cli-
mate class 3K3 acc. to DIN EN 60721-3-3 with extended tempera-
ture and humidity range)
Up to 2000 m above sea level
2