BROTJE BBS 15 C Beiblatt Seite 22

Wärmetauscher in neuer revision
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
GB
Servicing
3.2
Optimised setting for system controller LMS 14
System controller
Year of construction
Affected devices
Level/Note/Descrip-
tion
Engineer
Description
Engineer
Description
Engineer
Description
Installer
Description
Note
This section includes exclusively information for programming the system controller ISR-Plus LMS
14, which can be helpful during service work.
Level / Note /
Description
Engineer
Description
22
From June 2010 to November 2011
– WGB; serie E
– WGB-K; serie E
– WGB-S; serie E
– WBS/WBC; series E,F
– BBS; serie E
– BBK; series E,F
– BSK
– BGB; serie E
Line
2243
Lengthening the burner off time.
These are increased to reduce the cycles of the device. For too extreme tem-
perature fluctuations in the heating circuit during the transition time, this value
can also be reduced.
2456
Maximum shut off difference for heating circuit.
These are increased to reduce the cycles of the device. For too extreme tem-
perature fluctuations in the heating circuit during the transition time, this value
can also be reduced.
5050
Maximum storage temperature
This was increased, since this can cause an interruption of the charging due to a
storage temperature that is too high when executing the Legionella function.
6205
The delivery programming of the LMS can be recovered in these lines (as under
Line 31 in the display). However the fuse is not in the display, but rather in the
system controller ISR-Plus LMS, so that this is still available after the display is
replaced!
If the ISR-Plus LMS is described with a Service-Stick, then the basic setting is
also overwritten corresponding to the data on the Service-Stick. If this value is
present, it should be preferred over line 31, since the fuse in the display is pos-
sibly older.
Line
6230
Identification for the boiler type is saved in this line (parameter set and revi-
sion). This ID is helpful, for example, for the later use of the Service-LMS.
Newly revised heat exchanger
ISR-Plus LMS 14
New value
7 min.
10°C
69°C
Reset to default parameters
Value
Info 1 OEM
Old value
3 min.
7°C
65°C
274045-05 05.13