Herunterladen Inhalt Inhalt Diese Seite drucken

Johnson Controls FX10 Advanced Anleitung Seite 3

Inhaltsverzeichnis

Werbung

115.2
Ø 4
99
FX10-S-002_01 2003
Figure 3: Drilling template and board dimensions
Figure 4: Main board and expansion board connection
Technical Specifications
Power Requirements
Power Consumption
Relay Outputs
Ambient Operating
Ambient Storage
Control Accuracy
5
37
This document is subject to change without notice.
24 VAC/DC ±15%; 50/60Hz
11 VA at max load (17 VA if expansion connected)
Insulation
Digital input; Analog input; PWM output: Not insulated
Relay output: Insulated
Triac output:
Opto-insulated
DO1, DO2: SPST 8(3)A, 250 VAC relays (low power version)
OR
SPST 25A, 250 VAC relays (high power version)
DO3 ÷ DO9: SPST 5(2)A, 250 VAC relays
OR
0,5A/24 VAC triacs
DO6:
SPDT 5(2)A, 250 VAC relays
OR
0,5A/24 VAC triacs
-20°C to +70°C (-4°F to +158°F)
Conditions
10 to 95% RH (non condensing)
-30°C to +80°C (-22°F to +176°F)
Conditions
10 to 95% RH (non condensing)
Inputs
Accuracy (@ 20°C)
A99
± 0.5 (sensor not included)
NTC
± 0.5 (sensor not included)
Ratiometric
Resolution: 10 mV
Connections
Relay / triac outputs:
Fast-on AMP (62650-1 or 63650-1);
Inputs and PWM outputs:
®
Molex
(41671) use with: Housing: 3069;
Crimp Terminals: 2478 / 2578 / 8818; Cable: AWG 18
OR
Wago Cage clamp series 235-2xx;
Min cable cross section: 0.5 mm
Dimensions
157.5 x 115.2 x 26 mm (without plug-in cards)
(H x W x D)
Compliance
89/336 EEC directive: EN 61000-6-3 (EN 50081-1);
73/23 EEC directive:
UL 873
Range
-40 ÷ +100°C
0 ÷ +100°C
0.5 ÷ 4.5 V
, AWG 20
2
EN 61000-6-1 (EN 50082-1)
EN 60730

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Fx10 standard