measure combustion parameters and check that combustion is
stable and clean.
6.6 CHECKING THE THERMOSTATS
Inspect the thermostat burner as follows:
• Remove any air outlet connection ducts
• Find the thermostats fixed to the internal panel of the space
heater.
• Clean with a dry cloth, taking care not to cut or bend the capillary
tube.
6.7 CLEANING THE INTERIOR OF THE HEATER
For thorough cleaning, the heater can be cleaned and washed inside
and outside with water. It is however necessary to ensure that:
• the electrical cable is disconnected and unplugged from the
socket
• completely close all access panels
• do not use water jets at a pressure exceeding 70 bar at a distance
less than 30 cm
• completely dry all parts before reconnecting the electrical cable.
6.8 CLEANING THE COMBUSTION CHAMBER
To maintain the burner's high efficiency and prolong its life, the
procedure described in this paragraph must be done at least once at
the end of the work season or more frequently if there is an
excessive build-up of soot. Excessive soot may be caused by poor
chimney draught, poor fuel quality, poor regulation of the burner, or
more or less frequent alternation of burner starts and stops.
Pay attention during operation: pulsations at start may be due to
excessive amounts of soot..
To access the heat exchanger (1), take off the rear panel (3), remove
the smoke box inspection panel (2), and then remove baffle plates
(7).
To access the combustion chamber (4) remove the burner (5).
Clean with compressed air or, if necessary, with a metal brush to
L-L 255.00-RK
EN
remove any deposited soot and combustion residues.
Warning
After any technical work, always check that the heater
works correctly.

7. TROUBLESHOOTING

In the event of serious anomalies, various safety devices are able to
block the machine's operation and signal the same:
• on the electrical panel
the blocking signal following intervention by the safety
thermostat: the reset button is located on the thermostat
F+L1+L2 box.
(for three-phase models only) the blocking signal following
intervention by the motor thermal protection: the reset
button is located inside the electrical panel.
• on the burner
the blocking signal following intervention by the burner's
flame control box.
Warning
NEVER do more than two restarts in a row: unburned fuel
can accumulate in the combustion chamber and suddenly
flare up at the next restart.
If the heater is still not working properly, please contact your
nearest dealer or authorized Service Centre.