UL-Control Drawing

52
Connections
Hazardous Location
Class I, Division 2, Groups A, B, C, D; T4
Class II, Division 2, Groups F, G; T4
Class III
Class I Zone 2, Group IIC; T4
Class II Zone 22, Group IIIB; T85°C
Class III Zone 22, Group IIIA; T85°C
NI Apparatus
NI Apparatus
NI Apparatus
Notes
1.
The Entity Concept allows interconnection of non-incendive apparatus with associated apparatus not specifically
examined in combination as a system when the approved values of Voc (or Uo) and Isc (or Io) for the associated
apparatus are less than or equal to Vmax (Ui) and Imax(Ii) for the non-incendive apparatus and the approved values of
Ca(Co) and La(Lo) for the associated apparatus are greater than Ci + Ccable and Li + Lcable, respectively, for the non-
incendive apparatus,
Where Ccable= 60pF/ft if unknown
Where Lcable= 0.20uH/ft if unknown
2.
Simple apparatus: an electrical component or combination of components of simple construction with well-defined
electrical parameters that does not generate more than 1.5 V, 100mA, 25mW, or is a passive component that does not
disipate more than 1.3W and is compatible with the intrinsic safety of the circuit in which it is used.
3.
Wiring methods must be in accordance with all applicable installation requirements of the county in use. For US, this is
NFPA 70 (NEC) article 504 with additional information in ANSI-ISA –RP12.06.01. For Canada this is CSA 22.1-12 (CEC)
section 18 and appendix F.
Entity Parameters
Parameter
Maximum Output Voltage U
(V
)
o
oc
Maximum Output Current I
(I
)
o
sc
Maximum Output Power P
o
Maximum external capacitance C
(C
)
o
a
Maximum external inductance L
(L
)
o
a
This document contains safety-relevant information. It must not be altered without the authorization of a NE EX
Control Drawing for GXP Sysytem and TCU or PCU Non-incendive Outputs
Global
Hazardous Location
Class I, Division 2, Groups A, B, C, D; T4
Class II, Division 2, Groups F, G; T4
Class III
Class I Zone 2, Group IIC; T4
Class II Zone 22, Group IIIB; T85°C
Class III Zone 22, Group IIIA; T85°C
GXP TCU or PCU NI Outputs
Type 1
X3.1 / X3.5 – VCC
X3.2 / X3.6 – D-
X3.3 / X3.7 – D+
X3.4 / X3.8 – GND
Type 2
X4.1 / X5.1 - Us
X4.4 / X5.4 - TxD
X4.6 / X5.6 - RxD
X4.2 / X5.2 – GND
Type 3
X4.4 / X5.4 - TxD
X4.6 / X5.6 - RxD
X4.2 / X5.2 - GND
Type 1
4.92 V
182 mA
570 mW
11.5 μF
19.5 μF
26.5 μF
36.5 μF
9 μH
4 μH
3 μH
2 μH
Only valid as long as released in EDM
Type 2
Type 3
8.95 V
8.95 V
150 mA
58 mA
1.4 W
128 mW
57.5 μF
400 nF
1.9 μF
1 μH
199 μH
199 μH
date:
2017-AUG-28
116-B034A
sheet 1 of 1