REFRIGERANT GAS CHARGE
lf you need to install a length of pipe longer than standard (the length for which the unit is
pre-charged), you must add the appropriate refrigerant charge.
PRE-CHARGE (m)

ADDITIONAL CHARGE

(g/m)
METHOD
1. Calculate the refrigerant charge to be added considering the parameters specified in
the "LENGTH OF REFRIGERANT CONNECTIONS" section in tHs manual.
2. Connect the R410A refrigerant cylinder in a position where the liquid can be
Charged into the pressure gauge unit valve where the nitrogen cylinder or the
vacuum pump has been connected.
3. Connect the pressure gauge unit to the outdoor unit charging valve (gas). when
injecting the liquid refrigerant through the gas valve, you must act slowly and pay
attention so as to prevent liquid hammer to the compressor.
4. Place the refrigerant cylinder on an electronic scale.
5. Open the valve to allow the refrigerant to pass through.
6. Close the valve when the weight of the cylinder coincides with the amount to be
charged.