Herunterladen Inhalt Inhalt Diese Seite drucken

Programmable Parameters - IME M-Bus Conto D4-Pd Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für M-Bus Conto D4-Pd:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Programmable Parameters

1 CodE
Access password
Keep simultaneously pressed the
Load
Password 1000
and confirm
moves the cursor
Page
increases/decreases the loaded value
Prog
confirms
Page + Prog
2 ModE
Energy count configuration
Mode ASY
Partial energy count always active
Total energy (display T)
Total energy (display P)
Mode SYn
Partial energy count activated by the closing of the external contact
Total energy (display T)
Total energy (display P)
Partial energy count no active
C
D
Mode trf
Energy count with double tariff. Tariff switching with closing of the external
contact
(C - D terminals)
Energy tariff 1 (display
)
Energy tariff 2 (display
)
Energy Count tariff 1
C
D
06/16 10783381 WEB E cod.CE4DT06AM
2 keys
until you display page
Partial energy count active
C
D
Energy Count tariff 2
C
D
3 tiME
Integration time for average power calculation
Selectable values: 5 – 8 – 10 – 15 – 20 – 30 – 60 minutes
increases the loaded value
Prog
decreases the loaded value
Page
confirms
Page + Prog
4 M-Bus Communication
4.1 Addr
Address number
Selectable values: 1...250
moves the cursor
Page
increases the loaded value
Prog
confirms
Page + Prog
4.2 bAUd
Transmission speed
(C - D terminals)
Selectable values: 300 - 600 - 1200 - 2400 - 4800 – 9600 bit/s
increases the loaded value
Prog
decreases the loaded value
Page
confirms
Page + Prog
4.3 00000000
Secondary Address
Selectable values: 0...99999999
moves the cursor
Page
increases the loaded value
Prog
confirms
Page + Prog
Conto D4-Pd
5

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis