3.11.5 Timer

- The timer block is used to cretate a daily program to
initialise the operation time of the extra output (P3), this
function is generally use for energy saving in the case of an
additional heat source being used to warm the tank (e.g.:
additional heat is present only at the end of the day if the
sun loading was insufficient during the day.)
To use the Timer function select the line "Timer" and choose
"Yes", then there is the possibility of adjusting the "start" and
"stop" times for three blocks.

Settings
Delay
Timer
Time 1 Start
Time 1 Stop
Time 2 Start
Time 2 Stop
Time 3 Start
Time 3 Stop
3.12

Cooling Function

Available only if extra function "cooling" is selected on the
output P3
Water temperature on top of tank1 T3
(°C)
Cooling
start
Cooling stop
(start – hysteresis)
P3

3.12.1 Cooling start

- setting level to start cooling the tank1 (by activating P3
output) to another heat storage for example when the water
temperature in the top of tank1 (T3) is above this setting
level. (Adjustable 20 to 90°C with factory value 75°C)

3.12.2 Cooling hysteresis

- Value of the hysteresis to stop cooling the tank1 when the
water temperature on the top of tank (T3) is under Cooling
start temperature minus hysteresis value. (Adjustable 1 to
30°C with factory value 10°C)
3.13

Diff control Function

Available only if extra function "diff control" is selected on the
output P3.
MaxCold
Tank

dTMax

MinWarm
tank
3.13.1 Max cold tank
- Maximum level on tank1 to stop the exchange function (T3
= TC).
(Adjustable 15 to 95°C with factory value 65°C)
-
+900s
On
24H00
24H00
24H00
24H00
24H00
24H00
Warm storage TW
Cold storage TC

dTMin

Extra
P3
15
3.13.2 Min warm tank
- Minimum level on external tank to start the exchange
function (T4 = TW). (Adjustable 0 to 95°C with factory value
15°C)
3.13.3 dTMax
- Value of the difference between cold and warm storage to
start the exchange function. (Adjustable 3 to 40°C with
factory value 15°C)
3.13.4 dTMin
- Value of the difference between cold and warm storage to
stop the exchange function. (Adjustable 2 to 30°C with
factory value 7°C)
3.14

Antistagnation Function

Available only if extra function "Antistagnation" is selected on
the output P3.

Start level

Stop level

Standard
loading cycle
3.14.1 Start Level
- Setting level on collector (T1) to start the function, the
pump P1 will be turned on to discharge the warm
temperature of the collector through the relay P3.
(Adjustable 0 to 200°C with factory value 110°C)
3.14.2 Stop Level
- Setting level on collector (T1) to stop the antistagnation
function, the pumps P1 and P3 will be turned off. (Adjustable
0 to 150°C with factory value 90°C)

4 Operation Menu


Operation--------------- -- -----
Automatic
OFF
Chimney sweep
Manual testing
4.1

Automatic and Off operation

- To put your system in Automatic operation, press (+) or (-) to
select the "Automatic" line and press (►) to active this
working mode.
- To put your system in Off mode repeat the same sequence
as above.
Note: The controller status is displayed by a small graphic, on
the main screen stating "OFF"
Collector
(T1°C)
P3
Tank (T2°C)
P1
Antistagnation
cycle
(Active)