Grundfos sensors

- Your controller had 2 specials inputs for analogics sensors
GRUNDFOS (Type VFS Flow sensor or RPS pressure
sensor).
The Flow sensor is used for energy measuring and
supervision, the pressure sensor is used only to supervise the
pressure on the primary circuit.
GDS1 (Grundfos Direct Sensor)
Once the line selected press (►) to enter in the submenu
GDS1.

GDS1----
GDS1
NC
You will have the choice between Flow or Pressure sensor with
different scales.
To choose the type of the sensor connected press (►) to
highlight the line and select your choice with (+) or (-).
- "NC"
- "RPS 0 – 4 bar"
- "RPS 0 – 6 bar"
- "RPS 0 – 10 bar"
- "VFS 1 – 12l/min"
- "VFS 2 – 40l/min"
- "VFS 5 – 100l/min"
- "VFS 10 – 200l/min"
- "VFS 20 – 400l/min"
Sensor type: see type plate on the mounted sensor
- Following your sensor choice you can view the
instantaneous values of the temperature, flow or pressure
measured by the sensor.
With Flow sensensor "VFS",

GDS1----
GDS1
Flow
Temp GDS1
With Flow sensensor "RPS",

GDS1----
GDS1
Pressure
Temp GDS1

GDS2 (Grundfos Direct Sensor)

This input has the same function and possibilities of the GDS1
input,
2.5.3

Impulse Flow meter:

If impulse flow meter is installed (on T6 / PF) select "Yes", then
you must enter with (+) or (-) the flow meter characteristics in
liter / Impulse.
---
-
Not used
Pressure sensor
Pressure sensor
Pressure sensor
Flow sensor
Flow sensor
Flow sensor
Flow sensor
Flow sensor
---
-
VFS 1-12 l/min
x.x l/min
xxx°C
---
-
RPS 0 - 4 bar
x.x bar
xxx°C
(Adjustable 1 to 25 L/imp with factory value 10 L/imp)
When you use an impulse flow meter for energy measuring,
you must
Connect a temperature sensor (usually T5) mounted on the
collector return piping, to get the correct calculated energy
values.

Impulse flow meter no

Impulse flow meter Yes
Liter/impulse
Important Note:
You must not connect an impulse flow meter to T6, if a digital
pressure or flow sensor is connected to GDS2!
2.5.4

Temperature Sensor

This submenu allows viewing of the current state of all
temperature sensors connected on the controller; you can
immediately see the actual value measured by the sensor, if it
is in use or not & if the sensor is defective.

Temperature sensors
T1
T2
T3
T4
T5
By pressing on the on the (►) key, you will acced the
calibration of the sensor.

Pt1000
Calibration
Careful: Check the real value of the sensors with calibrated
thermometer before adjusting. (Calibration range -3 to +3°C
with factory value 0°C)
2.6

Energy measurment:

The controller has two energy measurement blocks. It is
possible to configure for both blocks the sensors which will be
used for energy calculation.
Energy metering calculation logic:
To calculate the energy the controller needs several elements,
two temperature measurement points "Warm" and "Cold", the
flow value and the heat transfer fluid properties.
11
T6
---
T6
---
10
Inputs
Configuration----
xxx°C
xxx°C
xxx°C
not used
not used
T1
---
0°C
-
-
-
-