Technical Information

Diagnosis Management

4
5
6
F
Table 8
Offset
0
1
2
3
4
5
6
7
8
168/178
Controller response was "Over range"
Controller response was "Bad operation"
Controller response was an unknown response
Parameter not supported by the controller family
Diagnostic Buffer Structure
Meaning
B
station non exist (set by master)
0
B
station not ready (slave not ready for data exchange)
1
B
cfg fault (configuration data doesn't match)
2
B
ext diag (slave has external diagnostic data)
3
B
not supported (slave doesn't support requested function)
4
B
invalid slave response ( slave sets permanent '0')
5
B
prm fault (wrong parameter assignment)
6
B
master_lock (slave is parameterised by another master)
7
B
prm req (slave has to be re-parameterised)
0
B
stat diag (static diagnosis)
1
B
fixed '1'
2
B
wd_on (response monitoring active)
3
B
Freeze mode (received freeze command)
4
B
Synch mode (received synch command)
5
B
reserved
6
B
diag deactivated (slave is parameterised by another master)
7
Reserved
Master Add (master address after parameterisation. FF= without
parameter)
Ident number high
Ident number low
External diagnosis "Header" length indication including header
Interface Status
B
Controller not responds
0
B
Controller not identified
1
B
Input data not fully coherent yet
2
B
Not used
3
B
Number of devices recognised on the low-speed network
4...7
Parametrisation diagnostic byte 0
TMP Profibus Gateway User Manual / 87-900-976-01 (F)