Anhang/Appendix; Typenschild/ Rating Plate Pke - Eaton PKE series Handbuch

Motorschutzschalter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

10/15 MN03402004Z-DE/EN
Typenschild/
Rating plate PKE

Anhang/Appendix

U
(V~)
lq = (kA)
50/60Hz
e
I
(A)
Type
400
440 500 690
e
PKE-12
100
12
20
10
XTPE012B
PKE-32
32
100
25
6
XTPE032B
U
= 6000 V
imp
IEC/EN 60947-4-1
0102
165628
THE OPENING OF THE BRANCH-CIRCUIT
PROTECTIVE DEVICE MAY BE AN INDICATION THAT A FAULT
CURRENT HAS BEEN INTERRUPTED: TO REDUCE THE RISK OF
FIRE OR ELECTRIC SHOK; CURRENT-CARRYING PARTS AND
OTHER COMPONENTS OF THE CONTROLLER SHOULD BE
EXAMNED AND REPLACED IF DAMAGED: IF BURNOUT OF
THE CURRENT ELEMENT OF AN OVERLOAD RELAY OCCURS,
THE COMPLETE DEVICE MUST BE REPLACED.
Abbildung/Figure 1:
Abbildung/Figure 2:
SEE DIAL FOR
MAX
MOTOR FULL-
HP
LOAD AMPS
BREAK ALL LINES
3 PH
3
3
TRIP RATING
1 PH
125% OF
DIAL SETTING
PKE/XTPE MAX RMS SYM AMPS MAX. FUSE MAX. C. B.
1,2 - 12
10 kA - 600V AC
150 A
125 A
32
10 kA - 600V AC
150 A
125 A
MAN.MTR.
CNTLR
340B
N4246
WARNING
Typenschild/Rating plate PKE12, PKE32
Typenschild/Rating plate PKE65
115
200
240
480
600
V
1.2
1/2
1/2
HP
4
3/4
3/4
2
3
HP
12
3
3
7 1/2
10
HP
32
5
7 1/2
15
20
HP
1.2
HP
4
1/8
1/4
1/3
HP
12
1/2
1
1 1/2
HP
32
1 1/2
3
3
HP
SUITABLE FOR GROUP INSTALLATION
WHEN PROTECTED BY ANY OF THE FOLLOWING:
- LISTED CURRENT LIMITING C.B. PER UL 489
- LISTED FUSE
RATED AS SHOWN IN TABLE AND
HAVING AN INTERRUPTING RATING NOT
LESS THAN INDICATED
FOR FIELD WIRING SEE
INSTALLATION INSTRUCTIONS
LISTED
57