Specifications
Line
Voltage
Ventilate
Model
frequency
(v)
setting
(Hz)
Lossnay
Energy
recovery
setting
50
LGF-100GX-E
230
Bypass
Ventilate
setting
* The values given in the table for the noise level reflect the levels measured at a position one meter away from the unit in an anechoic
chamber.
* Noise change or increase may occur because of the Bypass-Automatic function or Automatic fan speed change by timer setting.
* Temperature Exchange efficiency (%) are based on winter condition.

After-sales servicing

Consult with your dealer about the after-sales services provided for
this Lossnay product.
8
Power
Air volume
Fan
Current
consumption
speed
(A)
(W)
(m
3
/h)
EX-Hi
4.20
922
995
Hi
3.50
790
995
Low
3.45
785
890
EX-Hi
4.35
960
995
Hi
3.75
845
995
Low
3.70
840
890
Temperature
Static pressure
Exchange
efficiency (%)
(L/S)
(mmH
O)
(Pa)
2
276
20.4
200
80
276
15.3
150
80
247
12.1
119
81
276
20.4
200
-
276
15.3
150
-
247
12.1
119
-
If you hear strange sounds, if no air is blown out or if some other
trouble occurs, switch off the power and contact your dealer. Consult
with your dealer concerning the cost of inspection or repair work.
Enthalpy Exchange
Noise
Weight
efficiency (%)
(dB (A) )
(kg)
Heating
Cooling
72.5
71
49
72.5
71
47
74
72
44
164
-
-
51
-
-
49
-
-
46
(1mmH
O=9.80665Pa)