Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 222

Safety devices

Photocells
Confi gure the CX contact (NC), input for safety devices such as
photocells.
When programming the functions, the (F2) CX input can be set
to:
- C1reopening during closing. When the gate is closing, opening
the contact triggers the inversion of movement until the gate is
fully open again;
- C2close back up during opening. When the gate is opening,
opening the contact triggers the inversion of movement until the
gate is completely closed.
- C3partial stop. Stopping of the gate, if it is moving, with
consequent automatic closing (if the automatic closing function
has been entered);
-C4 obstruction wait. Gate stops, if it is moving, and once the
obstruction is removed, it resumes its movement.
 If unused, the CX contact should be deactivated during
programming.
 If you wish to add a second pair of photocells, make the
electrical connections by using input CY as show in the fi gure
and set the function on F3.
R X
R X
10 2 TX C NC
10 11 E TS 1 2 3 3P 4 5 7 CX CY
10 2 TX C NC
10 11 E TS 1 2 3 3P 4 5 7 CX CY
T X T X
TX 2
TX 2

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für Motostar SLS24

Inhaltsverzeichnis