5. VariTrans® P 43xxx D2
The housing width is 45 mm.
The devices isolate and transmit input
currents in the range of ±0.1 A ... ±5 A.
The individual measuring ranges are
calibrated.
The broad-range power supply operates from
20 ... 253 V AC/DC.
5.1 Product Line
• VariTrans® P 43000 D2 (-nnnn)
The working voltage for basic insulation (overvoltage category III,
pollution degree 2) is 2.2 kV. The 16 measuring ranges are selected using
an insulated rotary switch on the device front or by reconnecting the
input and/or output lines.
• VariTrans® P 43100 D2 (-nnnn)
The working voltage for basic insulation (overvoltage category III,
pollution degree 2) is 3.6 kV. The range is fixed to customer requirements
(single range devices).