Herunterladen Inhalt Inhalt Diese Seite drucken

Troubleshooting - Pentair Water RO-2600 Installations- Und Bedienungshandbuch

5-stufige umkehrosmoseanlage mit boosterpumpe
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25

TROUBLESHOOTING

Leaks between bottom of housing and cap
1. Ensure sump is tightly screwed to cap. If it still leaks close
the cold water supply and tank valves.
2. Remove housing and clean the black rubber O-ring.
Lubricate with clean silicone grease. With two fingers, insert
O-ring in groove below threads of housing and press into
place. Tighten housing back onto cap.
3. Open the cold water supply and tank valve. If leaks persist,
call Technical Support.
Leaks on tank valve assembly
1. Open drinking water faucet to drain storage tank. Let
drinking water faucet run until it drips. Turn off cold water
supply.
2. Push in on white collar of tank valve fitting and pull out
tubing. Unscrew the tank valve from the storage tank.
Rewrap threads on top of the tank with Teflon® tape. Screw
tank valve back onto tank. Trim 1/2-inch from end of tubing
and reinsert 5/8-inch into tank valve fitting.
3. Open the cold water supply and shut off the reverse
osmosis faucet. Let the system pressurize for several
hours and check for leaks. Check again after tank is fully
pressurized.
Leaks on quick-connect fittings
1. Close the cold water supply and tank valve.
2. Depress plastic collar and pull out tubing.
3. Cut off 1 inch of tubing and place a mark 5/8-inch from end
of tubing. Tubing should be cut squarely. The internal and
external burrs should be removed.
4. Push tubing 5/8-inch into fitting.
5. Open the cold water supply and tank valve. If leaks persist,
call Technical Support.
No flow or slow flow from the brine (drain) line
Less than 1½ cups per minute
NOTE: Before checking brine (or reject) flow, make sure
the system is producing water by turning off the
valve on the storage tank and opening the faucet.
Water should drip from faucet.
1. Examine the prefilters. If clogged, replace (see Replacing
the Prefilter and Postfilter Cartridges) and recheck the brine
(or reject) flow rate.
2. If the prefilters are not at fault, the brine (or drain) flow
controller is probably clogged. Call Technical Support.
High TDS in Product Water
If high levels of TDS (Total Dissolved Solids) are detected in
your product water (approximately 30% or greater of what is
measured in your tap water, as determined with a conductivity
meter or by a TDS Test Kit), the RO membrane may need to
be replaced, or the brine (or drain) flow control tubing may be
clogged. See your dealer or plumber to check product water
TDS.
Reduced production
Slow or no product water flow usually indicates either a
clogged prefilter or an exhausted membrane. First, replace
the prefilters. If the production rate is not improved, replace
membrane.
Gradual return of taste and odor
Gradual return of unpleasant taste and odor over a period
of time may indicate that your filter cartridges and/or RO
membrane need to be replaced. See Replacing the Prefilters
and Replacing the Reverse Osmosis Membrane.
Sudden return of taste and odor
If shortly after complete servicing noticeable taste and odors
return contact Technical Support.
No water pressure from the drinking water
faucet or low volume in storage tank
1. Close the cold water supply to system.
2. Lift storage tank to see if it is empty. If not, open the
drinking water faucet to empty water from tank.
NOTE: It may be necessary to pump a small amount of air
into the tank with a bicycle pump to remove all the
water from the tank.
3. When tank is empty, use a pressure gauge to check
tank pressure. An empty tank should contain 5 to 7 psi
pressure. Increase or decrease the air pressure in the tank
accordingly.
4. Open cold water supply. Let system run for
3 hours to fill tank, then check system performance. If
performance has not improved, call Technical Support.
Model RO-2600 5 StageReverse Osmosis System SE11 • 11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis