ply (figure 3 is typical) can be shared among multiple monitored
output circuits. If a supply is to be shared, between Monitored
Output Circuits wired to a common PCB, use the short power
supply jumpers shown on page 1. The jumpers can be used on
T11–T15. Refer to Table 4 for jumper functions.
TABLE 4
JUMPER LOCATION
T11
T12
T13
T14
T15
(–)
(–)
47K
(+)
(+)
Figure 2: Example of Class B, Style Y Monitored Output Circuit configuration with a single supply dedicated to a single
Monitored Output Circuit.
(–)
(–)
47K
(+)
(+)
Figure 3: Style Y Monitored Output Circuit configuration with a single supply shared by 2 Monitored Output Circuits.
D500-68-00
MONITORED OUTPUT CIRCUIT PAIR
SHARING SUPPLY
+0 and +1
+1 and +2
+2 and +3
+3 and +4
+4 and +5
EXTERNAL
47K
POWER
SUPPLY
VIO
VIO
LPOWER-LIMITED
TOP OF T0
AND SUPERVISED
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT
DEVICE
COMMUNICATION LINE 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
EXTERNAL
POWER
(–)
(–)
SUPPLY
47K
(+)
(+)
RED
BLK
VIO
VIO
POWER-LIMITED
TOP OF T0
AND SUPERVISED
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT
DEVICE
COMMUNICATION LINE 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
A supply can be wired to be shared among multiple PCBs in the
same cabinet (figure 4 is typical). To share among multiple PCBs:
use the long power supply jumpers (shown on page 1) to connect
either T10 or T16, of one PCB, to either T10 or T16 of the other
PCB.
An EOL relay must be used for every external power supply (fig-
ures 2–3 are typical). The EOL relay coil should always be con-
nected at the external power supply input of the module which
is connected farthest away from the power supply. The EOL relay
contacts should always be connected in series with the Monitored
Output Circuit wiring of the same module. The EOL relay coil
should be connected across the PS+ (red wire) and PS- (black
wire) if it is connected at T0 – T5. The EOL relay coil should be
connected across adjacent pins (red – even pin#, black – odd
pin#), of the same connector, if T10 – T16 are used.
All cabling must comply with local standards or codes of practice.
All external power supplies must be voltage regulated with bat-
tery back-up.
+
+
+
+
+
+
+
+
3
*Note 1:
EOL Relay Coil Connections must
be made using EOL Relay Connector
Assembles on T10-T16 in event that
all monitored Output Circuits on the
PCB have dedicated supplies.
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
4
4
3
3
2
2
1
1
0
0
A/B SELECT
DISABLE 1
DISABLE 2
DISABLE 3
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
4
4
3
3
2
2
1
1
0
0
A/B SELECT
DISABLE 1
DISABLE 2
DISABLE 3
STATUS
INDICATORS
STATUS
INDICATORS
I56-2253-01