Salda FLEX Bedienungsanleitung Seite 14

Steuerungspult mit lcd-bildschirm
Vorschau ausblenden Andere Handbücher für FLEX:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 18
EN
5.
"View sensors"
Values of all connected sensors are displayed.
Note: Number of the displayed sensors depends on the configu-
ration of the controlled board
"Efficiency" % - efficiency of the heat exchanger based on exhaust
air temperature
"Supply air temp." °C (TJ)
"Room air temp." °C
"Extracted air temp." °C (TA)
"Outdoor air temp." °C (TL)
"Exhaust air temp." °C (TE)
"Ret. water temp." °C (TV)
"Preheat air temp." °C
"Supply humidity" %
"Extract humidity" % (DR)
"Outdoor humidity" %
"Supply pressure" %, Pa
"Extract pressure" % Pa
"Extract CO2" %, ppm
"Heating" %
"Cooling" %
"By-pass valve" %
6.
"Extra"
Additional settings from the controlled recuperator.
6.1.
"Exit" – return to the menu window
6.2.
"ModBus" – settings of the ModBus protocol
6.2.1. "MBAddress" 0-247 (*1)
6.2.2. "Parity", *None, Odd, Even
6.2.3. "Baudrate"
Possible data transmission speeds
2'400, *4'800, 9'600, 19'200, 38'400 kbps
6.2.4. „Stop"*1 or 2 stop bits
6.3.
"Vent.Ctrl."
6.3.1. "Mode" – select the type of ventilation:
"Supply" – based on the supply air temperature
"Room" – based on the extracted air temperature
"ByOutDoor" – - ventilation operates using the supply
or extracted air temperature based on the set „OutDoor
T.C" value of the ambient air temperature (see. 6.3.4).
When the outdorr air temperature exceeds the set
value, ventilation operates using the extracted air
temperature and, when the ambient air temperature is
lower than the set temperature, supply air temperature
is used.
6.3.2. "Min Supply" – lowest allowed supply temperature,
12-24°C (*15°C)
6.3.3. "Max Supply" – highest allowed supply temperature,
25-40°C (*40°C)
6.3.4. "OutDoot T.C" – summer/winter temperature setting,
10-30°C (*16°C)
6.4.
"Cool.Ctrl." – cooling control
6.4.1. "Min Supply" – minimum supply air temperature when
cooled, 0-15°C (*6°C)
6.4.2. "DX_coolOn" – chlorofluorocarbon cooling is switched
on at "Cool PI", % (*23%)
14
System V2.2
Date - Time
View Alarms
Languages
Sensors values
Extra
View sensors
Exit
Supply air temp.
Extract air temp.
Outdoor air temp.
Extra
Exit
ModBus
Vent. Ctrl.
Cool. Ctrl.
Add. Func.
100%
Cool PI
DX_ON
DX_OFF
www.salda.lt
6/7
20.2 °C
19.2 °C
-2.3 °C
1/10
76 %
20.2 °C
19.2 °C
-2.3 °C
0%