 A qualified technician should install and service this device.
 The measurements provided by this device are for information
purposes only.
Description
Three-phase four-wire electronic watt-hour meter with pulse
counting output. Very accurate, reliable, light and compact device.
Connection diagram: see page 2.
Features
 LCD display (with blue backlight)
 pulse output
 LED indicator
Reset
This device does not have a reset function.
Technical Specifications
dimensions
voltage
current
accuracy class
frequency
display mode
power consumption ≤ 2 W (10 VA)
temperature range
LED indicator
pulse output
10(100)A: 10  (Ib = 10 A) and (100)  I max = 100 A.
(1)
The internal measurement always happens at 10 A (Ib), this
via an internal voltage divider. For example, a live current of
25 or 32 A flows through the circuit. The max current for this
kwh meter may be 100 A (I max).
Note: the most accurate measurement for these kWh meter, is
by a live current of 10 A through the circuit.
V. 07 – 16/08/2018
EMDIN03
7 modules DIN-RAIL
3 x 230 / 400 V
10 (100) A
(1)
1.0
50 / 60 Hz
LCD 6+1 = 999999.9 kWh
-20 to 55 °C
1 blink per pulse
800 imp/kWh
voltage: 12 to 27 V
current: 27 mA
impulse width: 90 ms