Changing the factory settings
The opening range, closing range and afterflow are factory preset (see Technical data). Use the
Oras Data Terminal (Oras no. 6910) to adjust those settings where required.
Connecting Oras Data Terminal
– Close the water inlet to the faucet by simultaneously lifting and turning the temperature
adjustment handle, clockwise as far as it goes.
– Detach the electronics casing by undoing the locking screw (3) with a 2 mm Allen key and turning
the casing 90° clockwise.
– Detach the clip (4) holding the electronics box (5) inside the casing and then lift the box out of the
casing.
– Undo the screws (7) from the cover (6) of the electronics box and open the cover.
– Connect the Data Terminal and make the adjustments.
– Reassemble in reverse order.
– Open the water inlet to the faucet by turning the temperature adjustment handle anti-clockwise.
If required, please seek the best possible advice at an expert HVAC store.

Troubleshooting

SYMPTOM
The water flow from the spout
does not stop or stops only
after 2 minutes.
The water flow has diminished
over time.
No water comes from the faucet.
Audio signal (once every five seconds).
(figure 4)
CAUSE
– Sensor is dirty, obstructed or broken.
– Recognition range is too long.
– Solenoid valve is damaged.
– Litter filters are blocked.
– Aerator is dirty.
– Check the water inlet to the faucet.
– Sensor is dirty, obstructed or broken.
– Recognition range is too long.
– Solenoid valve is damaged.
– Sensor is dirty, obstructed or broken.
– Recognition range is too long.
– Battery voltage is too low.