Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - S+S REGELTECHNIK THERMASREG ALTR Bedienungs- Und Montageanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
®
THERMASREG
Mechanical temperature controllers ⁄ contact thermostats THERMASREG
controlling and limitation of temperatures at pipes or vessels, e.g. in connection with hot-water or floor heating systems. The contact temperature
®
controller THERMASREG
ALTR is built as one-step device, as adjustable temperature controller TR (with external setting) or as adjustable tem-
perature monitor TW (with internal setting).

TECHNICAL DATA:

Switching capacity: ................. 16 (4) A; 24...250 V AC
(Contact load)
Contact: ............................... dustproof switch block unit as
Max. sensor temperature: ........ 110 °C
Enclosure: ............................. ABS (acrylonitrile butadiene styrene),
Enclosure temperatur: ............. - 35 °C ...+ 65 °C
Tolerance: ............................. T
Sensor element: ..................... bimetal
Enclosure dimensions: ............. 38 x 48 x 103 mm
Process connection: ................ by metal tension spring, 220 mm long
Electrical connection: .............. 0.14 - 1.5 mm
Protection class: .................... I (according to EN 60 730)
Protection type: ..................... IP 40 (according to EN 60 529)
Standards: ............................ CE conformity,
FUNCTION:
Heating: ................................ wire contacts C - 1
Cooling: ................................ wire contacts C - 2
Type ⁄ WG2
ALTR 060 ⁄ 090
A LT R - 0 6 0
A LT R - 0 9 0
ALTR 060 ⁄ 090 U
A LT R - 0 6 0 U
A LT R - 0 9 0 U
ALTR 060 ⁄ ALTR 090
(For further information see table!)
at 24 V AC min. 150 mA
potential-free single-pole changeover contact
fibre-glass reinforced,
base: steel, galvanised, top: grey,
M 16 x 1.5
± 5 K; T
± 5 K
min
max
(included in the scope of delivery)
2
via terminal screws
EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 2006 ⁄ 95 ⁄ EC
Temperature
Thermal Operating
Range
Difference (fixed) ca.
0 ...+ 60 °C
+ 20 ...+ 90 °C
0 ...+ 60 °C
+ 20 ...+ 90 °C
®
ALTR with switching output (two-position controller) for monitoring,
Max. Capillary
Temperature
8 K (± 1 K)
+ 110 °C
8 K (± 1 K)
+ 110 °C
8 K (± 1 K)
+ 110 °C
8 K (± 1 K)
+ 110 °C
Connecting diagram
C
2
1
Item No.
TR
(External setting)
1102- 1040-1100- 300
1102- 1040-1101- 000
TW (Internal setting)
1102- 1040-2100- 300
1102- 1040-2100- 400
ALTR 060
ALTR 090

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis