THERMASREG
Mechanical temperature controller THERMASREG
working as capillary thermostat ⁄ capillary controller without external voltage.
This capillary controller is used for monitoring and to control temperatures of non-aggressive liquid or
gaseous media in heating, ventilation and air conditioning technology as well as in mechanical and apparatus
engineering, for installation in immersion sleeves or air conditioning ducts.
TECHNICAL DATA:
Switching capacity: ................. 24...250 V AC +10 %, 16 A, cos ϕ = 1.0
(Contact load)
Contact: ............................... dust-proof switch block unit as
Enclosure: ............................. plastic, material polyamide, 30 % glass-globe-reinforced,
Enclosure dimensions: ............. 108 x 70 x 73.5 mm (Thor II)
Cable gland: ........................... M 20 x 1.5; including strain relief
Enclosure temperature: ........... –10...+65 °C
Design principle: ..................... torsion meter with liquid filling
Sensor:................................. copper tube, length of capillary = 1 m
Tolerance: ............................. T
Inserted length: ...................... immersion sleeves EL = 150 mm
Electrical connection: ............. 0.14 - 2.5 mm
Protection class: .................... I (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity, EMC directive 2004 ⁄ 108 ⁄ EC,
FUNCTION:
Heating: ................................ wire contacts 2 - 3
Cooling: ................................ wire contacts 2 - 1
Type ⁄
WG2 ⁄ 01
TR xx - F
T R -1- F
– 35 ... + 35 °C
T R - 0 6 0 - F
T R - 0 9 0 - F
T R - 012 0 - F
T R - 5 014 0 - F
+ 50 ...+ 140 °C
Extra charge:
U = Internal setting (TW), e.g. TR - 090 -F - U
TR -F
®
TR x x - F with remote sensor and switching output (one-step),
(For further information see table!)
24...250 V AC +10 %, 1.5 A, cos ϕ = 0.6
at 24 V AC min. 150 mA
potential-free single-pole changeover contact
colour traffic white (similar to RAL 9016)
with PVC protective hose, Ø 6.8 mm
± 3 K; T
± 3 K
min
max
2
via terminal screws
low-voltage directive 2006 ⁄ 95 ⁄ EC
Temperature
Thermal Operating
Range
Difference (fixed) approx.
0 ... + 60 °C
0 ... + 90 °C
0 ...+ 120 °C
Max. Capillary
Temperature
3 K (± 1 K)
+ 60 °C
3 K (± 1 K)
+ 75 °C
3 K (± 1 K)
+ 120 °C
5 K (± 1 K)
+ 135 °C
5 K (± 1 K)
+ 150 °C
Rev. 2015 - 1.0 GB
Connecting diagram
2
1
3
Item No.
TR
(External setting)
1102-1056- 1110- 100
1102-1050- 1110- 300
1102-1050-1110- 400
1102-1050-1110- 500
1102- 1050-1110- 600
TR - F