Configuration using Switches: Example

Sensor:
Measuring range:
Output signal:
1. Adjust input sensitivity:
1.5 mV/V
The nominal value lies in the range 1.00 ... 1.99 mV/V:
Set the range (1+S/100): DIP1 = DIP2 = 0, DIP3 = 1
Number to the right of the decimal point (rotary switches): 50
2. Adjust zero point (see specifi cation on the sensor):
-0.13 mV/V
Set the range –(0+Z): DIP4 = DIP5 = DIP6 = 0
Set the number (rotary switches):
3. Adjust output signal:
4 ... 20 mA:
Compression load cell,
nominal value: 1.5 mV/V
Zero: -0.13 mV/V
0 ... 1.5 mV/V
4 ... 20 mA
DIP7 = 0, DIP8 = 1
Note
Cover the switches with the included
self-adhesive polyimide tape after
completion of confi guration.
13