Herunterladen Inhalt Inhalt Diese Seite drucken

Configuration Using Switches: Example - Knick PolyTrans P 32000 P0 Serie Handbuch

Universal-messumformer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Configuration using Switches: Example

Sensor:
Measuring range:
Output signal:
1. Adjust sensor type:
TC Type J:
2. Adjust start value:
200 °C
This start value is composed of: numerical value = 20, factor = x10.
Adjust numerical value using rotary switches:
Adjust factor x10:
3. Adjust end value:
1200 °C
For end values above 1000 °C, adjust factor x10 + 1000
Adjust numerical value using rotary switches:
Adjust factor x10 + 1000:
4. Adjust output signal:
4 ... 20 mA:
Thermocouple type J
200 ... 1200 °C
4 ... 20 mA
DIP1 = 1, DIP2 = 0, DIP 3 = 0
DIP7 = 0, DIP8 = 1
Note
Cover the switches with the included
self-adhesive polyimide tape after
completion of confi guration.
20
DIP4 = 0, DIP5 = 1
20
DIP6 = 1
55

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis