ANNEX 4 - BACNET REGISTER LIST SUMMARY
Instance
BACnet Type
ObjectName
Number
Status
Multistate Input
1
STATUS_AHU
Binary Input
24
WV01_B_State
Binary Input
25
KV01_B_State
Setpoints
Analog Value
4
TT02_MV1
Analog Value
14
PT03_MV1
Analog Value
16
QT01_MV1
Analog Value
17
PT04_MV1
Analog Value
20
PT05_MV1
Activate values from BMS
Binary Value
10
TT06_M_Comm_Act
Binary Value
12
TT05_M_Comm_Act
Binary Value
15
QT01_M_Comm_Act
Values from BMS
Analog Value
99
TT06_M_Comm
Analog Value
101
TT05_M_Comm
Analog Value
104
QT01_M_Comm
Binary Value
1
Free_Cooling_Comm
Binary Value
3
OW01_B_Comm
Binary Value
6
TS01_B_Comm
Binary Value
7
RS01_B_Comm
Fire Alarm
Binary Value
2
BM01_A_Comm
Binary Value
31
SF01_SV5
Binary Value
32
EF01_SV5
Analog Value
26
SF01_SV4
Analog Value
30
EF01_SV4
Binary Input
9
BM01_A_State
Alarms
Binary Input
26
DM01_B_State
Binary Input
27
DM02_B_State
Binary Input
2
SF01_A1_State
Binary Input
10
SF01_A_State
Binary Input
3
EF01_A1_State
Binary Input
11
EF01_A_State
Binary Input
7
TA02_A_State
Binary Input
31
PS01_A_State
Binary Input
32
PS02_A_State
Readings
Description
Unit status
Heat demand
Cold demand
Desired supply temperature
Desired static supply duct pressure
Desired room air quality
Desired flow supply fan normal speed
Desired flow extract fan normal speed
Activate outdoor temperature via communication
Activate room temperature via communication
Activate room air quality via communication
Outdoor temperature via communication
Room temperature via communication
Room air quality via communication
Activate Nightcooling
Activate Occupancy / Out of hours override
Activate Change-over status
Activate Reset Alarms
Activate Fire alarm
Action supply fan when fire alarm
Action extract fan when fire alarm
Desired command supply fan fire alarm
Desired command extract fan fire alarm
Fire alarm
Alert, service needed
Alarm, go to unit
Supply fan pressure failure
Supply fan failure
Extract fan pressure failure
Extract fan failure
Frost protection booster coil
Filter guard supply filter
Filter guard extract filter
BACnet Reg.List v4.014 summary
NOTE: The list can be different for each software version.
BACnet Status
1 = Status Off, 2 = Fire alarm, 3 = Max. temp. elect.
heater, 4 = Frostprotection, 5 = Recirculation, 6 =
Low outdoor Start-up, 7 = Start-up, 8 =
Nightcooling, 9 = Change speed, 10 = Normal run,
11 = Stopping
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
-
-
-
-
-
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
-
-
-
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Cold, 1 = Warm
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Off, 1 = On
0 = Off, 1 = On
-
-
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
0 = Inactive, 1 = Active
Unit
Function
-
Read
-
Read
-
Read
°C
Read/Write
Pa
Read/Write
ppm
Read/Write
m³/h Read/Write
m³/h Read/Write
-
Read/Write
-
Read/Write
-
Read/Write
°C
Read/Write
Read/Write
°C
ppm
Read/Write
-
Read/Write
-
Read/Write
-
Read/Write
-
Read/Write
-
Read/Write
-
Read/Write
-
Read/Write
%
Read/Write
%
Read/Write
-
Read
-
Read
-
Read
-
Read
-
Read
-
Read
-
Read
-
Read
-
Read
-
Read
64