Herunterladen Inhalt Inhalt Diese Seite drucken

S+S REGELTECHNIK HYGRASGARD RPFF Montageanleitung Seite 15

Vorschau ausblenden Andere Handbücher für HYGRASGARD RPFF:
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

  • DEUTSCH, seite 3
G
®
HYGRASGARD
Quality product for HVAC sector, accuracy 3 % r. H.
The calibrateable pendulum room humidity sensor HYGRASGARD
converts the measurand humidity into a standard signal of 4 ... 20 mA. Relative humidity (in % r. H.) is the quotient of water vapour partial pressure
divided by the saturation vapour pressure at the respective gas temperature. HYGRASGARD
ambiences in refrigeration, air conditioning, ventilation and clean room technology, hotels, technical rooms, meeting rooms and convention centres.
These measuring transducers are designed for exact detection of humidity. A digital long-term stable sensor is used as measuring element for
humidity measurement. This sensor is applicable for duct installation, as pendulum feeler, or for integrating it into equipment.
TECHNICAL DATA:
Power supply: ........................ 15 ... 36 V DC (± 10 %), (depending on working resistance)
Power consumption: ................ < 1.1 VA ⁄ 24 V DC
Sensors: ............................... digital humidity sensor
Sensor protection: .................. membrane filter, plastic sinter filter, exchangeable
Measuring range, humidity: ....... 0 ...100 % r. H.
Operating range, humidity: ....... 0 ... 95 % r. H. (without formation of dew)
Deviation, humidity: ................. ± 3 % r. H. (20...80 %) at +20 °C, otherwise ± 5 % r. H.
Output, humidity: .................... 4 ... 20 mA, working resistance < 500 Ω,
Ambient temperature: ............. storage - 25 ...+ 50 °C
Long-term stability:................. ± 1 % per year
Electrical connection: .............. 2-wire connection (see connecting diagram), 0.14 - 1.5 mm²
Cable length: ......................... 1.5 m (other lengths optional on request)
Protective tube: ..................... metal,
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity,
®
HYGRASGARD
RPFF - LC
Type ⁄ WG1
RPFF - LC - I
R P F F - L C - I
Extra charge:
For special orders
please specify:
Accessories
MF-16-K
RPFF - LC
dew-proof, small hysteresis, high long-term stability
(output corresponding to 4 ... 20 mA)
see load resistance diagram
operation - 5 ...+ 55 °C
L =100 mm + 25 mm, Ø =16 mm
according to EMC directive 2004 ⁄ 108 ⁄ EC,
according to EN 61326-1: 2006,
according to EN 61326-2-3: 2006
Measuring Range
Humidity (relative)
0 ...100 % r. H.
2-wire connecting leads (PVC) per running meter
Type, cable length
e.g. RPFF-LC-I, 3 m; RPFF-LC-I, 4 m
Description
Mounting flange, plastic
®
RPFF - LC with plastic sinter filter measures the relative humidity of air. It
Output
Humidity (relative)
4...20 mA
15
®
RPFF - LC applied in non-aggressive dust-free
2-wire
connection
+UB 24V DC
brown
Output humidity
white
in % r.H. 4-20mA
Item No.
I - variant
1201- 1172- 0000-150
Item No.
7100-0030- 0000- 000
RPFF - LC - I
(Transmitter)
Inhaltsverzeichnis
loading

Inhaltsverzeichnis