Herunterladen Diese Seite drucken

S+S REGELTECHNIK HYGRASGARD RPFF Montageanleitung Seite 14

Vorschau ausblenden Andere Handbücher für HYGRASGARD RPFF:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

  • DEUTSCH, seite 3
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier also allows operating 0 - 10 V devices on AC
supply voltage.
The output signal is to be tapped by a measuring instrument. Output
voltage is measured her against zero potential (O V) of the input voltage!
When this device is operated on DC supply voltage, the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground
wire!
When several devices are supplied by one 24 V AC voltage supply, it is to
be ensured that all "positive" operating voltage input terminals (+) of the
field devices are connected with each other and all "negative" operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
NOTE
For 4 ... 20 mA devices, DC voltage must be used (without residual
ripple, see permissible range of load resistance diagram). Do not use
pulsating DC voltage.
Load resistance diagram
Load resistance diagram
4 ... 20 mA
800
700
600
500
400
300
250
200
50
10
15
Operating voltage (V DC)
RPFF ⁄ RPFTF
RPFF - 25 ⁄ RPFTF - 25
Admissible
range
20
25
30
35 36 40
Connecting scheme
Power supply
AC 24V~
0V
DC 15-36V = GND
Connecting scheme
Power supply
AC 24V~
0V
DC 15-36V = GND
Load resistance diagram
Load resistance diagram
4 ... 20 mA
500
400
300
200
100
50
10
Operating voltage (V DC)
14
Individual operation
Circuitry
V
Parallel operation
Circuitry
Circuitry
Admissible
range
15
20
25
30
35 36 40
RPFF - LC

Werbung

loading