FIXING THE GATEWAY ASSEMBLY, USING THE
RAV SERIES:
The Gateway device may be sited in any convenient
indoor position though it is recommended that it be
situated as close as possible to the indoor unit.
It may be wall mounted, fixed in ceiling voids or
incorporated into a control panel or similar
enclosure; details of dimensions and fixing centres
together with cable entry points are outlined in
Figure 5 of the Dimensions section.
WIRING THE GATEWAY TO THE INDOOR UNITS,
USING THE RAV SERIES:
Connect a 230V AC supply to the IEC Plug supplied and
then connect the plug to the Gateway using the retaining
clip. Interconnect the XY terminals on the Gateway PCB to
the XY terminals on each indoor unit, using 2 core screened
cable. Ensure continuity of the screen throughout and
connect one end of the screen only to the earth at the
terminal provided on the Windows
connect any other part of the screen to earth to avoid
possible signal degradation. See Figure 1.
FIXING THE GATEWAY ASSEMBLY, USING THE MM SERIES:
The Gateway must be sited in an indoor position though it is
recommended that it be situated as close as possible to the outdoor unit.
It may be wall mounted, fixed in ceiling voids or incorporated into a control panel or
similar enclosure; details of dimensions and fixing centres together with cable entry points
are outlined in Figure 5 of the Dimension sections.
WIRING THE GATEWAY TO THE OUTDOOR UNIT, USING THE MM SERIES:
Connect a 230V AC supply to the IEC Plug supplied and then connect the plug to the
Gateway using the retaining clip. Interconnect the XY terminals on the Gateway PCB to the
XY terminals on the outdoor unit (master outdoor unit – inverter), using 2 core screened
cable. Ensure continuity of the screen throughout and connect one end of the screen only to
the earth at the terminal provided on the Windows
of the screen to earth to avoid possible signal degradation. See Figure 2.
SETTING THE INDOOR UNIT ADDRESSES:
Before the system can work with the Windows
addresses. Allocate one address number from 1 to a maximum of 64 to each of the indoor
units. This series of numbers must be sequential and can be in any order i.e. if the Gateway
is connected to 20 units, the address must be 1 to 20.
Two units should not be set to the same number. We recommend that the layout is recorded
using the tables at the end of this manual.
®
Windows
Gateway – Installation

Fixing and Wiring the Gateway Assembly

®
Gateway. Do not

Setting the Addresses

GB
Connect to A-I Network
terminals, X & Y throughout
2 core screened
240V AC mains supply
2 core L
®
Gateway. Do not connect any other part
®
Software, it is essential to set the indoor unit
6
Figure 1.
Continue to 64 units
®
W
Network Cable
ON
ORKS
Figure 2.
XY
PQ
up to 64
Indoor Units
240V AC mains supply
®
2 core L
W
Network Cable
ON
ORKS
Wiring
Wiring