Product Information / Produktinformation A6120
Bearing Vibration Monitor
2. Carefully pull the controller board off the main board without tilting it. The position of the J2
jumpers on the main bard is identified with a white frame in the following figure.
3. To switch the raw sensor signal to terminals z14 and z 16 place the jumpers as shown in b).
If the jumpers are set as shown in a) then the dynamic portion of the sensor signal is applied
on terminals z14 and z16.
SENS1
z14:
z16:
SENS2
4. Place the controller board back on the main board and secure it with the four screws. Now,
the raw sensor signal is on the connection strip.
Installation
1. Check the slot wiring prior to installing the monitor.
2. Push the A6120 monitor into the prepared slot and press it with light pressure into the plug
connector.
3. Hand tighten the two anchoring screws on the front panel to secure the monitor.
Any other information, e. g. shielding and grounding, configuration of the monitor, etc., can be
found in the direction for use "Bearing Vibration Monitor A6120", order number: 6110−90002.
AC1
SENS1
z14:
J2
z16:
SENS2
AC2
a)
Page 12
AC1
J2
AC2
b)