The product can be damaged if the gas cylinder is moved!
Entrained liquid phase can cause the pressure to increase in the LPG system and damage
the product or the LPG system.
Do not move the gas cylinder while the system is in operation.

TROUBLESHOOTING

Fault cause
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Abnormal flame pattern of
non-adjustable pressure
regulator
Abnormal flame pattern
of adjustable pressure
regulator
No gas flow
OPSO cannot be unlocked
Pressure gauge indicates
incorrect values or is not
working at all.
part no. 05 239 50 j
1st stage regulator Type VSR 0523, VSR 0524 and VSR 013
Action
 Close the gas supply.
 Do not use any electric switches.
 Do not use a phone in the building.
 Ventilate rooms well.
 Shut down the LPG system.
 Contact a specialised company.
Compare the nominal outlet pressure with the nominal
connection pressure:
 if they do not correspond, replace the pressure regulator
or the gas appliance
Measure the outlet pressure; outlet pressure is not within
the specified limits:
 check the system configuration
 pressure regulator is defective, replace
 check the gas filter
Compare the nominal outlet pressure of the pressure
regulator with that of the connected device:
 If they do not match, adjust the pressure regulator to the
nominal connection pressure
Measure the outlet pressure of the pressure regulator;
outlet pressure is not within the specified limits.
 Check the system configuration
 Readjust the outlet pressure
Gas feed is closed:
 open the gas cylinder valve or the shut-off fittings
Safety overpressure shut-off valve (OPSO) is closed:
 carry out the steps described in "Restarting the safety
overpressure shut-off valve (OPSO)"
Filter sieve in the input connection is dirty:
 send the pressure regulator to the manufacturer to be
checked
Regulator membrane is damaged:
 Pressure regulator is defective, replace.
Pressure gauge is defective.
 Replace only when the LPG system is completely
de-pressurised.