Herunterladen Inhalt Inhalt Diese Seite drucken

Advantages And Equipment - GOK VSR 013 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für VSR 013:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Risk of asphyxiation from gas leaks in enclosed spaces!
High concentrations of gas can cause difficulty in breathing and lead to unconsciousness.
A discharge line must be connected from the breather

ADVANTAGES AND EQUIPMENT

Filter screen in the inlet connection of the pressure regulator
LPG may contain foreign matter, such as dirt particles. Over a certain size, these particles are
trapped in the filter screen in the inlet connection. If the LPG is not filtered, wear and tear of
the LPG system is increased up to complete failure. See TROUBLESHOOTING.
Safety overpressure shut-off valve OPSO
The OPSO - (Over-Pressure Shut Off) is an automatic safety device that protects connected
devices against excessive high pressure. The outlet pressure is monitored constantly. If the
outlet pressure is exceeded, the OPSO responds and the gas feed is interrupted. The visual
display switches from GREEN to RED.
When it has responded, the OPSO must be opened manually. If the OPSO responds, the
gas feed can be restarted again by following the steps in "Restarting the safety overpressure
shut-off valve OPSO / UPSO". If an OPSO is installed, the pressure regulator is also marked
"OPSO" on the type label.
Pressure relief valve PRV
The pressure relief valve (PRV) is an automatic safety device with limited flow that is installed
in the pressure regulator to protect connected devices against inadmissible high pressures. If
there is inadmissible high pressure at the outlet side, for example due to high temperatures,
the PRV opens and relieves the excess pressure through the breather. When the pressure
falls, the PRV closes again automatically.
A connection to the open air must be created if a pressure regulator with PRV is to be
operated indoors, inside housing or in any other areas that could be at risk.
"PRV" is marked on the type label of the pressure regulator.
Risk of asphyxiation from gas leaks in enclosed spaces.
High concentrations of gas can cause difficulty in breathing and lead to unconsciousness.
A discharge line must be connected from the breather
outdoors.
To do this, install the ventilation set (see LIST OF ACCESSORIES) to discharge any
escaping LPG outdoors.
Emergency supply connector option
In case of unforeseen events, such as the gas tank becoming empty, the gas supply can be
maintained until the gas tank is refilled with the help of a gas cylinder and the emergency
supply set.
The gas cylinder is not intended for permanent supply. It is intended only as a temporary
solution until the gas tank has been refilled.
With the emergency supply set (Part No. 02 498 00) connect a gas cylinder to the emergency
supply connector (G 3/8 LH-KN) of the pressure regulator.
part no. 05 239 50 j
1st stage regulator Type VSR 0523, VSR 0524 and VSR 013
,
or
of the PRV to outdoors!
,
or
on the product to
5 / 16

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für GOK VSR 013

Diese Anleitung auch für:

Vsr 0523Vsr 0524

Inhaltsverzeichnis