Safety Notes; Transport, Storage And Packaging; Technical Data - oventrop Regufloor HC Einbau- Und Betriebsanleitung

Regelstation für flächenheizung und -kühlung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2 Safety notes

2.1 Correct use
Safety in operation is only guaranteed if the control
unit is used correctly.
The control unit "Regufloor HC" is used for flow tem-
perature control or surface heating and cooling sys-
tems.
Any use of the control unit outside the above applica-
tions will be considered as non-compliant and misuse.
Claims of any kind against the manufacturer and/or
his authorised representatives due to damages caused
by incorrect use cannot be accepted.
The observance of the installation and operating in-
structions is part of the compliance terms.
2.2 Possible dangers at the installation location
The case of an external fire has not been taken into
consideration when constructing the control unit.
WARNING
Heavy control unit
Risk of injury Suitable transport and lifting devi-
ces are to be used. Wear suitable protective clot-
hing (e.g. safety shoes) during installation and use
safety devices. External components like hand -
wheels or pressure test points must not be misu-
sed for the absorption of external forces, e.g. as
connection point for lever tools etc.
Hot and cold surfaces
Risk of injury Do not touch the control unit without
safety gloves. It may get very hot during operation.
Sharp edges
Risk of injury Store and install the control unit out
of reach of children.
Small components
Risk of ingestion Store and install the control unit
out of reach of children.
Allergies
Health hazard Do not touch the control unit and
avoid any contact if allergies against the used ma-
terials are known.
3 Transport, storage and
packaging
3.1 Transport inspection
Upon receipt check delivery for any damages caused
during transit.
Any damage must be reported immediately upon re-
ceipt.
6
3.2 Storage
The control unit "Regufloor HC" must only be stored
under the following conditions:
– Do not store in open air, keep dry and free from dust.
– Do not expose to aggressive fluids or heat sources.
– Protect from direct sunlight and mechanical agita-
tion.
– Storage temperature: –20°C up to +60°C,
max. relative humidity of air: 95 %
3.3 Packaging
Packaging material is to be disposed of environmen-
tally friendly.

4 Technical data

4.1 Performance data
Control unit
Max. operating pressure p
Max. differential pressure:
Max. operating temperature
t
primary side:
s
Max. operating temperature
t
secondary side:
s
k
value:
vs
Performance range:
Pump:
Technical data of the pump is detailed in separate
operating instructions.
Fluid: Non-aggressive fluids (e.g. water and suitable
water and glycol mixtures according to VDI 2035). Not
suitable for steam, oily and aggressive fluids.
DANGER
Suitable measures (e.g. safety valves) have to be
taken to ensure that the maximum operating pres-
sures and maximum and minimum operating tem-
peratures are not exceeded or undercut.
4.2 Dimensions/Connection sizes
316
Illustr. 4.1 Dimensions with actuator (optional)
:
6 bar
s
0.75 bar
90˚ C
50˚ C
4
up to 15 kW or a
heating surface up to
200 m
2
with a heat
demand of 75 W/m
2
100
134
~145
Depth inside
the cabinet