Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English

Connection Hints

Power Supply and Signal Output
Direct Cable Connection: Solid or stranded conductor with connector sleeve for conductor
cross-sections from 0.5 mm
of the connecting cables (power supply and signal output) must be at least AC 300 V.
Tightening Torque: min 0.5 Nm
The rated current of the device is 0.5 A. To ensure proper selectivity in the fusing sequence,
the power supply line is to be equipped with a minimum 2 A circuit breaker (the maximum
value depends on the wiring of the cabinet). The circuit breaker must be installed close to
the device. The circuit breaker must be marked as a switch for the device.
Fibre Optic
Please observe the permissible bending radius of the optical fibre waveguide. Bending
cables to a smaller radius than the bending radius may destroy the optical fibres.
30
2
2
to 2.5 mm
Warning
Do not look directly into the fibre-optic elements or cables!
, corresponding to AWG 22 to 12. The rated voltage
Sync-Transceiver
E50417-K1074-C294-A2

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

7ke6000-8al/dd

Inhaltsverzeichnis