Herunterladen Inhalt Inhalt Diese Seite drucken

Daikin EKOMB28AAV1H Installationsanleitung Seite 49

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 57
side.
8.3.8
CH installation stays warm unwanted
Possible causes:
Room thermostat/weather dependent regulation
faulty or short circuited.
No È
CH installation is heated due to Tap comfort.
The service display regularly shows code 7.
8.3.9
A-label pump LED flashes intermittently red/green
Possible causes:
Too high or too low mains voltage.
No È
Pump temperature is too high.
8.3.10 A-label pump LED flashes red
Possible causes:
Pump stopped.
Daikin Europe NV
Solution/cause:
Check the wiring.
Check OpenTherm and On/off connection of the unit.
Yes Æ
Replace the thermostat.
Replace the weather-dependent regulation.
Unwanted circulation in the CH circuit due to thermosiphon effect or second pump in
Yes Æ
the CH circuit. Install a check valve in case of thermosiphon effect or a two-way
valve in case of a second pump.
Solution:
Yes Æ Check the mains voltage.
Yes Æ Check the water and ambient temperature.
Solution:
Reset the pump by switching off the unit by pressing the on/off button for at least 20
seconds
(attention: if the pump has been set to continuous, the pump can only
Yes Æ
be reset by pulling the plug from the socket).
Replace the pump.
49

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Diese Anleitung auch für:

Ekomb22aav1hEkomb33aav1h

Inhaltsverzeichnis