Herunterladen Inhalt Inhalt Diese Seite drucken

Daikin EKOMB28AAV1H Installationsanleitung Seite 17

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 57
Underfloor heating distributor without pump
Connect the underfloor heating system (D) and set the maximum CH supply temperature of
the boiler to the design condition. Fit a clamp thermostat (A) onto the supply tube
underneath the boiler. The clamp thermostat with blind cap must be set to a maximum
supply temperature of 55°C.
Assemble the on/off room thermostat (B) and connect it in series with the clamp thermostat
to connector X4 - 6/7 in the unit. See par. 10.1.
In this situation, the pump in the boiler is used to bridge the loss of pressure of the
underfloor heating system. Using the loss of pressure graph par. 7.4, the maximum loss of
pressure of the underfloor heating system can be determined.
Make sure there is a minimal water circulation. See par. 7.3. If required, install a by-
pass valve (C).
In case of an underfloor heating system without pump, we recommend changing the
following parameter settings:
par. o from 0 to 3.
par. P from 5 to 2.
Parameter 3 must also be set to its minimum level, or the
transmission loss of the property.
Daikin Europe NV
17

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Diese Anleitung auch für:

Ekomb22aav1hEkomb33aav1h

Inhaltsverzeichnis