Connecting the DHW cylinder on the water side

System schematics with all recommended valves ( Fig. 9, page 46).
Item
Description
1
Storage cylinder
2
Air vent valve
3
Shut-off valve with drain valve
4
Pressure Relief Valve
5
Non-return valve
6
Stop valve
7
DHW circulation pump
8
Pressure reducer valve (if required)
9
Test valve
10
Non-return component
11
Pressure gauge connector
AB
DHW outlet
EK
Cold water inlet
EZ
Circulation inlet
Table 7 System schematics ( Fig. 9, page 46)
▶ Use installation material that is heat-resistant to 160 °C (320 °F).
▶ Never use open, vented expansion vessels.
▶ Use metal connection fittings in potable water heating systems with
plastic lines.
▶ Size the drain line in accordance with the connection.
▶ To facilitate debris removal, never install elbows in the drain line.
▶ If using a non-return valve in the cold water supply: Install a pressure
relief valve between the non-return valve and cold water inlet.
▶ Install a pressure reducer if the static system pressure is in excess of
5 bar.
5.2.2

Installing a pressure relief valve (on site)

▶ Install a type-tested pressure relief valve on site that is approved for
potable water (DN 20) in the cold water supply ( Fig. 9,
page 46).
▶ Observe the pressure relief valve installation instructions.
▶ Terminate the discharge pipe of the pressure relief valve where it will
be easily visible in the frost-proof area via a dewatering point.
– The discharge pipe must be at least equal to the outlet cross-
section of the pressure relief valve.
– The discharge pipe must be able to discharge at least the flow rate
that is feasible at the cold water inlet ( Tab. 4, page 25).
▶ Attach a notice with the following text to the pressure relief valve:
"Never close the discharge pipe. During heating, water may be
discharged for operational reasons."
If the static system pressure exceeds 80 % of the pressure relief valve
excess pressure:
▶ Install a pressure reducer upstream ( Fig. 9, page 46).
Gas supply
Pressure relief
pressure
valve excess
(static
pressure
pressure)
6 bar
< 4.8 bar
5 bar
6 bar
8 bar
5 bar
8 bar
6 bar
7.8 bar
10 bar
Table 8 Selection of a suitable pressure reducer
W 120-5 O – 6 720 819 306 (2018/10)

Pressure reducer

in the EU
outside the EU
not required
max. 4.8 bar
not required
max. 5.0 bar
not required
max. 5.0 bar
not required
5.3

Installing the hot water temperature sensor

Install the hot water temperature sensor at the test point [4] to measure
and monitor the DHW temperature in the DHW cylinder
( Fig. 3 page 45).
▶ Install the hot water temperature sensor ( Fig. 10, page 47).
Ensure that the sensor surface has contact with the sensor pocket
surface over its full length.