8. Menu guidance
8.3 Main menu "Configuration"
Function
Language
Setting the language
Setting range:
- dEU (GEr): German
- EnG:
English
Contrast
Setting range:
1 - 4
Reset
A reset is used to reset all settings of the digital indicator to the factory settings.
The SELECT key must be pressed twice to activate the reset.
After pressing the key once, the RESET display starts flashing and after the
second actuation of the key, the display is completely hidden and the reset is
carried out.
USER-unit
The user can freely program a 6-digit user unit.
The 6 characters can be selected from an alphanumeric character set.
By pressing the SELECT key, the first digit is enabled and starts flashing. Use
the arrow keys to select the desired character. By pressing the SELECT key
again, the character is confirmed and the next digit is enabled.
Min. failure message
Setting the current value which releases the min. failure message when this
value is reached or not reached.
The min. failure message is displayed with 5 underscores (_ _ _ _ _) and the
message OUTMIN.
Setting range: 3.5 ... 3.9 mA
Max. failure message
Setting the current value upon reaching or exceeding of which the max. failure
message is released.
The max. failure message is displayed with 5 upper scores (_ _ _ _ _) and the
message OUTMAX.
Setting range: 20.1 ... 21.5 mA
Firmware version
The number of the firmware version used is displayed.
WIKA operating instructions models DIH50, DIH52
EN
Factory setting
EnG
2
-----
USER
3.6
21.0
-----
21