Switches 2, 3: System Voltage
Three (3) system voltage configurations are available as
shown in the table below:
System Voltage
Auto
12
24
NOTE: Before connecting the battery, measure the open-circuit
voltage. It must be over 10 volts to start the controller. If the
system voltage Settings Switches are set to Auto-detect, battery
voltage over 15.5V will be detected as a 24V nominal battery,
and the unit will charge accordingly. The 12/24V auto selection is
only done at start-up, and the detected system voltage will never
change during operation.
Generally, the specfic system voltage is known, and it is best
to set DIPs 2,3 accordingly; the auto-detect setting should
be used only in rare circumstances.
Switches 4, 5, 6: Battery Type Selection
Preset EcoBoost MPPT battery charging options are shown
in table 3-1 below. All voltage settings listed are for nominal
12 volt batteries.
Multiply the voltage settings by two (2) for 24 volt systems.
NOTE: These settings are general guidelines for
use at the operator's discretion. The
EcoBoost MPPT can be programmed to satisfy a wide range
of charging parameters. Consult the battery manufacturer for
optimal battery charge settings.
12
Installation
Switch 2
Switch 3
OFF
OFF
OFF
ON
ON
OFF
DIP
Absorp.
Float
Equalize
Switch
Battery
Stage
Stage
Stage
Settings
Type
(volts)
(volts)
(volts)
4-5-6
off-off-off 1 - Sealed*
14.00
13.50
off-off-on 2 - Sealed*
14.15
13.50
14.40
off-on-off 3 - Sealed*
14.30
13.50
14.60
off-on-on 4- AGM/Flooded
14.40
13.50
15.10
on-off-off 5 - Flooded
14.60
13.50
15.30
on-off-on 6 - Flooded
14.70
13.50
15.40
on-on-off 7 - L-16
15.40
13.40
16.00
on-on-on
8 - Custom
Custom
Custom
Custom
* "Sealed" battery type includes gel and AGM batteries
Table 3.1. Battery charging settings for each selectable battery type
Switch 7: Battery Equalization
Mode
Manual Equalization
Auto Equalization
Switch 8: Reserved for Future Use
EcoBoost MPPT Operator's Manual
Absorp.
Equalize
Equalize
Equalize
Equalize
Equalize
Equalize
Equalize
Time
Time
Timeout
Interval
LVD
LVR
Interval
Interval
(volts)
(volts)
(mins)
(mins)
(mins)
(days)
(days)
(days)
150
11.50
12.60
150
60
120
28
11.30
12.80
150
60
120
28
13.00
11.50
180
120
180
28
11.70
13.20
180
120
180
28
11.90
13.40
180
180
240
28
12.10
13.60
180
180
240
14
12.30
13.80
Custom
Custom
Custom
Custom
Custom
Custom
Custom Custom
Custom
Switch 7
OFF
ON
13