6. Commissioning, operation
Once the cover of the case has been removed, to configure the instrument
continue as follows:
To access the menu, while the actual value is displayed, press key 2 for 2
seconds until "dP" appears in the display.
To set the parameter values, press keys 2 and 3.
To save the set value, press key 1. The parameter name will then appear in
EN
the display once more.
To switch to the next parameter, press key 1. The name of the parameter
will appear in the display.
Parameters of the A-IAI-1 attachable indicator
Parameters Values
Key 1
dP
di.Lo
di.Hi
Li
18
If, during input, no key is pressed for 60 seconds, the configu-
ration of the instrument will be interrupted. Previously-saved
values will not be lost.
Description
Keys 2 and 3
Position of the decimal point (decimal point)
----
Max. indication range: -1999 ... 9999
---.-
Max. indication range: -199.9 ... 999.9
Max. indication range: -19.99 ... 99.99
--.--
-.---
Max. indication range: -1.999 ... 9.999
Lower indication range limit (display low)
-1999 ... 9999 This value will be displayed when the input signal
= 4 mA
Upper indication range limit (display high)
-1999 ... 9999 This value will be displayed when the input signal
= 20 mA
Measuring range limit (limit)
oFF
deactivated
Exceeding the measuring range limits is permitted
up to the measuring limit (see note)
on.Er
active, (error display):
The measuring range is limited exactly to the input
signal. When this exceeds or drops below it, a
corresponding error message is displayed.
WIKA operating instructions attachable indicator model A-IAI-1