Herunterladen Inhalt Inhalt Diese Seite drucken

V2 LEX-KNX20 Handbuch Zur Inbetriebnahme Seite 24

Lex-knx serie
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PAGE 5: AUTOMATIC OPERATION MANAGEMENT
Specific parameters for AWNINGS mode
AwSunThreshold
Values:
10 .. 100 [kLux]
Default:
10
AwSunOpenDelay
Values:
0 .. 255 [min]
Default:
8
AwSunCloseDelay
Values:
0 .. 255 [min]
Default:
8
PAGE 6: V2 SPECIFICATIONS
V2 Specific Parameters
VerboseLevel
Values:
- No message
- Only replies to
datapoint "Custom"
- All messages
Default:
Only replies to
datapoint "Custom"
Threshold used for comparison with the brightness of an ambient received on the "Brightness Main Value,
"Brightness Value #2" and "Brightness Value #3" datapoints to decide when to open or retract the awning.
The set value indicates the brightness in thousands of Lux.
Opening delay of the awning. The awning is opened when the ambient brightness level, received on the
"Brightness Main Value", "Brightness Value #2" and "Brightness Value #3" datapoints, remains over the
SunSensorThreshold threshold for the time set.
The set value indicates the time in minutes.
Delay in retracting the awning. The awning is closed when the ambient brightness level, received on the
"Brightness Main Value", "Brightness Value #2" and "Brightness Value #3" datapoints, remains under the
SunSensorThreshold threshold for the time set.
The set value indicates the time in minutes.
You can establish what messages received from the microcontroller of the motor must be sent on bus tin the
"Custom" datapoint:
Do not send any messages
When a telegram arrives on the "Custom" datapoint, which is sent to the motor, the first message
received from the motor is sent on the bus: this message is the response of the microcontroller to the
message received from the bus
Any incoming message from the motor is sent on the bus, therefore also stop and error messages.
- 24 -

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Lex-knx40Lex-knx50