Further components for the boiler
feedback
Install further components (e.g. relay module
HC60NG/R6660D) in accordance with the enclosed
installation instructions.

6. Electrical installation

DANGER
Danger to life through electric
shock!
Contacts that are open are live.
Ensure that the device is de-
energised.
Have all the work carried out by
authorised qualified personnel.
Observe the valid IEE regulations
during the installation.
WARNING
Damage to exposed components!
Destruction of the electronic
components through electrostatic
discharges.
Do not touch the components.
Touch an earthed piece of metal to
discharge static electricity from your
body.
6.1.
Electrical installation of Universal
Mixing Valve Controller HM 80
6.1.1.

Opening the housing

Open the housing as shown in Fig. 5 on the fold-out page.
6.1.2.

Permissible cable types and lengths

Power and pump connection 230 V~
Outer cable
Min. 5.0 mm/max. 10 mm
diameter
Cable length
Max. 100 m
Terminal range
0,3–1,6 mm²
Stripping length
6 mm
Cable type
NYM-J
Flow temperature sensor
Outer cable
Min. 5.0 mm/max. 10 mm
diameter
Cable length
Max. 100 m
Terminal range
0,3–1,6 mm²
Stripping length
7 mm
Cable type
Flexible/Rigid
Earthed connection
Terminal range
0,3–2,7 mm²
Stripping length
8 mm
Tab. 2: Permissible cable types and lengths
6.1.3.

Securing cables with a cable gland

Secure the cables with the
enclosed Eurofix cable glands in
accordance with the following
graphic.
Observe the installation
instructions for Eurofix.
6.1.4.

Connecting a power cable (230 V~)

DANGER
Danger to life through electric
shock!
Contacts that are open are live.
Ensure that the device is de-
energised.
Select a suitable cable in accordance with Table 2 for the
power supply.
Strip the connections 7 mm.
Connect the cable to the
connector in accordance with the
graphic (see fold-out page,
Fig. 3 (8)).
Connect the earthed connection
(PE conductor) in accordance
with the following graphic.
Secure the cable with the cable clamp.
Electrical installation
2
1
4
3
25