BTL5-A/C/E1_ -M _ _ _ _ -SF-F _ _
Micropulse Transducer - Rod Style
EU Directive 2004/108/EG (EMC Directive) and EMC law
Noise immunity: EN 61000-6-1 / EN 61000-6-2
Emission: EN 61000-6-3 / EN 61000-6-4
Intended use
The BTL5 Micropulse Transducer, together with a machine
controller (e.g. PLC), comprises a position measuring
system. It is intended to be installed into a machine or
system. Flawless function in accordance with the
specifications in the technical data is ensured only when
using original BALLUFF accessories, use of any other
components will void the warranty.
Opening the transducer or non-approved use are not
permitted and will result in the loss of warranty and liability
claims against the manufacturer.
General safety notes
Installation and startup may only be performed by
trained specialists.
The operator is responsible for ensuring that local safety
regulations are observed. In particular, the operator must
take steps to ensure that a defect in the position
measuring system will not result in hazards to persons or
equipment.
If defects and unresolvable faults occur in the transducer, it
should be taken out of service and secured against
unauthorized use.
User's guide download
A complete user's guide can be downloaded from the
Internet at www.balluff.com/downloads-btl5 or
requested via e-mail from service@balluff.de.
Dimensions and function
The transducer contains the waveguide. A float is moved
along the waveguide. This float defines the position to be
measured on the waveguide.
Ensure vertical mounting! The BTL is shown in a
horizontal position in the Figure.
BTL housing
70.5
1
english
Float
1)
BTL-S-3112-4Z
69
2
Nominal length = measuring range
48.8
Tank full
Installing the transducer
NOTICE!
Interference in function
Improper installation can compromise the function of the
transducer and result in increased wear.
► Only vertical mounting from above is permitted!
► The mounting surface of the transducer must
make full contact with the mounting surface and
be perfectly sealed through the use of a seal and
tri-clamp.
► Mounting must be done in a manner where the rod
cannot touch the container wall. Deflection of the
rod to the side, e.g. through flow currents, must
be prevented by a suitable, cleanable bracket or
appropriate positioning in the tank.
3-A Sanitary Standard Inc.
This product has authorization number 1486
and only corresponds to the specifications from
3-A SSI Inc. if used in conjunction with a
BTL-S-3112-4Z or BTL-S-3112-4Z-SA10 float
and the cotter pin included in the scope of
delivery for the float.
Installing the float
1. Install the float (accessory) taking the orientation into
account (raised markings on top).
2. Secure the float using the cotter pin included in the
scope of delivery, without placing any mechanical
loads on the rod. Guide the cotter pin through the hole
until it engages.
Installing the transducer
1. Insert a suitable seal.
2. Place the transducer on the mounting surface, so it
makes full contact and perfectly seals the hole.
3. Fasten the transducer with a 1 1/2" tri-clamp.
Tank empty
74-06
Cotter pin
1)
82
Not included
1)