Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
WARNING
!
Hazardous voltages are present in certain parts of this electrical equipment during operation.Incorrect handling of the
equipment can result in death, severe personal injury or substantial property damage. Only qualified personnel are allowed
to work on or around this equipment. The successful and safe operation of this equipment is dependent upon proper
transport, storage and installation.
Before installation or maintenance work is carried out, the main switch must be switched off and locked to prevent it from
being switched on again. If these rules are not adhered to, contact with live parts or improper use can result in death or
severe personal injury.
CAUTION
The device may only be opened by qualified personnel. Electrostatically sensitive devices (ESD)
Description and construction
The SITOP 24V/5A and 10A power supplies are built-in units. The devices must be installed in accordance with the relevant DIN/VDE
standards or national codes of practice.
Primary switched-mode power supplies for connection to 1-phase AC systems or to 2 phases of three-phase systems (TN, TT or IT
systems in accordance with VDE 0100 T 300 / IEC 364-3) with rated voltages 120 V / 230V , 50/60Hz or to a DC system in the 240V to
350VDC range, output voltage +24V DC, floating, short-circuit-proof and stable at no load.

Technical data

6EP1333-1AL12
6EP1334-1AL12
Input data
Rated input voltage U
:
e
1AC 120/230V
50/60Hz
or DC 240V-350V
(voltage selector in DC operation always set to
230V, optional polarity of connection to L and N)
Operating voltage range:
85V...132V, 170...264V
Surge resistance:
to EN 61000-4-1 A.2
Mains buffering at 93V/187V :
20ms
20ms
Input current I
at 120/230V:
e
2.4/1.5A
4.8/3.0A
rms
Making current limitation (25°C) standard
2
32A, 0.8A
s
65A, 3.3A
Recommended circuit-breaker characteristic C,
min 6A.
min 10A
Efficiency at full load and 230V AC(typical):
88%
89%
Power consumption (active power):
136W
270W
Installation instructions
Mount on standard DIN rail DIN EN 50022-35x15/7.5. To ensure proper cooling, the device must be mounted vertically such that the input
and output terminals are at the bottom. A clearance of 50 mm in each case must be left above and below the device.
The supply voltage connection must be made in accordance with VDE 0100 and VDE 0160. An interrupter must be provided for safe
disconnection of the power supply.
Connections and terminal assignment
Terminals
Function
L1, N (L2)
Input voltage
PE
Protective earth conductor
1, 2
Output voltage DC 24 V
SIEMENS AG ÖSTERREICH, 03.2002
Output data
Output DC voltage U
Delivery state: 24V ±1%
Setting range: 24V to 28.8V, set via potentiometer
on front of unit
Derating at U
a
4% I
or 3°C t
a
Output voltage ripple:
<100mV
residual ripple
pp
<200mV
peaks
pp
Direct output current I
0-5A
Two identical devices can be connected in parallel
to increase the power output.
rms
Environment
Temperature
2
s
for storage and shipment:
for operation:
Humidity rating according to climatic category 3K3
to EN 60721, Part 3; no condensation
Natural air cooling
Weight
0.60 kg
Terminal range
0.14 to 2.5mm
AWG 22 to 12
0.14 to 2.5mm
AWG 22 to 12
:
a
> 24V:
/ V U
amb
a
:
a
0-10A
-25°C to +85°C
0 to +60°C
0.72 kg
Remarks
2
Screw-type terminals. Use a screwdriver with a blade width of
3.5 mm. Recommended tightening torque 0.5-0.7 Nm
2
Screw-type terminals. Use a screwdriver with a blade width of 3.5mm.
Recommended tightening torque 0.5-0.7 Nm
4/8
Protective and monitoring
functions
Static current limitation: typ. 1.15 x I
Behavior under short-circuit conditions (output):
Cyclical restart
Signaling:
LED green:
Output voltage >20V
Standards
Degree of protection: IP20 to IEC 529
Class of protection 1 to IEC 536
Safety to VDE 0805 (EN 60950): SELV
Safety separation afforded according to EN60950;
EN 50178;VDE 0100 Part 410; EN61140+EN
60947-1 (equivalent to VDE 0140+VDE 0660 Part
100, replacing VDE 0100 Part 101)
Interference emission to EN50081-1
RI suppression according to EN 55022, limit-value
curve B
Interference immunity to EN 61000-6-2
UL 508, CSA 22.2
English
a
SITOP Power 5/10

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sitop power 10

Inhaltsverzeichnis